New research supported by ASHRAE indicates that non-chemical devices (NCD) marketed to control the growth of biological agents may not materially reduce biological growth.


https://facilityexecutive.com/2010/09/cooling-tower-study-results-released/
New research supported by ASHRAE indicates that non-chemical devices (NCD) marketed to control the growth of biological agents may not materially reduce biological growth.
Facebooktwittergoogle_plusredditpinterestlinkedintumblrmail

Cooling Tower Study Results Released

Cooling Tower Study Results Released | Facility Executive - Creating Intelligent Buildings

New research supported by ASHRAE indicates that non-chemical devices (NCD) marketed to control the growth of biological agents, such as Legionella in cooling towers, may not materially reduce biological growth.

Research project No. 1361, Biological Control in Cooling Towers Using Non-Chemical Water Treatment Devices, a two year project recently completed by Dr. Radisav Vidic at the University of Pittsburgh, evaluated five non-chemical devices using different technologies to control biological activity in a model cooling tower system. The devices studied included a hydrodynamic cavitation device, pulsed and static electric field devices, an ultrasonic device and a magnetic device.

In Vidic’s research, none of the non-chemical devices measurably reduced planktonic or sessile microbial populations in comparison to no-treatment tests and to a conventional chemical microbial control treatment protocol. The findings appear to be inconsistent with previous research by non-chemical device manufacturers and some independent researchers on some of the same devices tested in the ASHRAE study. Those other studies reported measurable degrees of biological control within the parameters of testing conducted.

“These results suggest that equipment operators, building owners, and engineers should consider taking more frequent water sample tests for their systems that rely on NCDs for biological control. If the testing shows an issue, one possible measure is to add chemical treatment capability to their system to prevent a potential health hazard from developing until additional research and field testing can resolve this question,” according to Vidic.

The study results are still subject to final approval by the sponsoring technical committee, TC 3.6 – Water Treatment. For notice of when the report is available, please contact Mike Vaughn, manager of research and technical services at ASHRAE.

You Might Like:

  • NCMS Report Finds Exoskeletons Prevent InjuryProductivity and safety improvements were revealed when the National Center for Manufacturing Sciences studied use of Lockheed Martin's FORTIS exoskeleton at a U.S. Navy shipyard.
  • The Well Living Lab Announces First Alliance MembersThe Well Living Lab leverages and expands upon the principles of the WELL Building Standard™ (WELL), which focuses on seven concepts relevant to indoor health—air, water, nourishment, light, fitness, comfort and mind.
  • Friday Funny: Finally Hanging Ten In AustinTexas Hill Country is probably the last place surfers would expect to hang ten, but that’s exactly what they’re doing now that some legal battles have ended.
  • Preventing Pee In The PoolIf your facility has a pool, keeping people happy and healthy in the water while creating a clean water experience for all can be a challenge.

1 COMMENT

  1. I have seen several other electro-chemical devices that have been proven to control scale, corrosion and micros. However, do not do business with R** C********** from e***. He has cheated at least 8 customers and reps out of money…just ask around. He has given this promising technology another black eye. BEWARE!

LEAVE A REPLY