Have a nice weekend!

Advancements In Smoke Detectors

The updated UL 268, Standard for Smoke Detectors for Fire Alarm Systems will be in effect June 2021.

By Erik Jackvony, EIT and Wayne D. Moore, P.E.
From the April 2020 Issue

Smoke detection devices are utilized in fire alarm systems throughout the world as a means of detecting fires in their earlier stages and subsequently notifying all occupants of the fire in the building or area protected. Where required to be installed by any nationally recognized code or standard, such as those issued by the International Code Council (ICC) or the National Fire Protection Association (NFPA®), system smoke detection devices are required to be listed for the purpose for which they are used. Underwriters Laboratories (UL) is perhaps the most globally recognized safety certification company, and is certainly among the most widely utilized, accepted, and trusted certification companies with regard to fire protection and life safety equipment.

smoke detection devices
Flaming Polyurethane Foam Test

For a fire alarm system smoke detector to bear the UL certification mark, it is required to comply with the UL 268 Standard for Safety, Smoke Detectors for Fire Alarm Systems. According to UL, the UL 268 Standard for Safety sets forth requirements for smoke detectors to be employed in indoor locations in accordance with the National Fire Alarm and Signaling Code, NFPA® 72.

Currently, most manufacturers of UL listed smoke detectors list their devices to the 6th Edition of UL 268, which has been in effect for the last decade. UL recently finalized and released the 7th Edition of UL 268, however manufacturers are not yet required to comply with its requirements. The effective date for the 7th Edition of UL 268 is June 30, 2021 . After this date, manufacturers will no longer be able to manufacture and label smoke detectors listed under the 6th Edition.

smoke detection devices
Smoldering Polyurethane Foam Test

UL 268 7th Edition has extensive revisions, the most prominent of which being the introduction of three (3) new detection performance tests. These new tests include:

  • a flaming polyurethane foam test
  • a smoldering polyurethane foam test
  • a cooking nuisance test

Due to the extent of the new and revised requirements, UL has indicated that new requirements will have a major impact on all currently listed smoke detectors. UL also anticipates that all the older version smoke detectors (manufactured to the 6th Edition of UL 268) will need to be redesigned to meet the requirements outlined in the 7th Edition.

smoke detection devices
Cooking Nuisance Test
(All photos: Edwards)

The new flaming and smoldering polyurethane tests were added to ensure that newly manufactured smoke detectors perform adequately and in a timely manner when installed in modern building construction environments. Over the past few decades, a drastic shift in the types of commonly used building materials has been made. New engineered and synthetic materials, such as polyurethane foam, have quickly taken the place of the natural materials which were used in building construction years ago. The concern related to this shift in building materials is that they generally burn much hotter and faster than the natural materials that they have replaced. Several studies and tests have shown that escape times available during a fire event have also drastically decreased in structures with the newer construction materials. Given these factors, smoke detectors listed to the 7th Edition of UL 268 will be required to demonstrate greater sensitivity to the smoke produced by fires in newly constructed buildings.

The new cooking nuisance test has been added for the exact reason that you would expect, to reduce the number of smoke detector nuisance activations caused from cooking activities. Regardless of the occupancy use classification of a building, nuisance alarms are never desired as they create unnecessary costs and fire department responses, cause interruption to the occupants, and in some cases can have negative impacts on occupant evacuation response as well as possible injury to first responders. Smoke detectors listed to the 7th Edition of UL 268 will be required to demonstrate increased resilience to nuisance smoke detector activations due to cooking activities.

Creating a smoke detector which satisfies the requirements of the three new fire tests, in addition to the existing fire tests, presents quite a challenge for smoke detector manufacturers. While the challenge is unique, it is not impossible. There is at least one manufacturer who has chosen early adoption of the revised standard and is now manufacturing their smoke detection devices to the 7th Edition of UL 268.

The early adoption of the 7th Edition of UL 268 is important and advantageous to engineered systems distributors, engineering specifiers, AHJs, installing contractors, and end users in many ways:

  • For the engineered systems distributor, stocking the new 7th Edition listed smoke detectors gives a competitive advantage in that smoke detectors listed to the 7th Edition of UL 268 translates to a very marketable device. Having the most technologically advanced, nuisance activation resistant and stable smoke detector available makes for an easy pitch to installing contractors and end users alike. Additionally, following the effective date for the implementation of 7th Edition of UL 268, distributors will rest assured knowing that they will not find themselves with a backstock of detectors which are no longer listed to the appropriate edition of UL 268. For the engineering specifier whose core values include achieving the highest level of life safety and reliability in their fire alarm system designs, specifying a UL 268 7th Edition smoke detector meets both core values. Designing a reliable system results in a satisfied end user who is more likely to retain and recommend your services.
  • For AHJs the obvious benefit of not dealing with multiple responses to false alarms will be a major cost saving (to the jurisdiction).
  • For the installing contractor, a quiet system without nuisance activations means less call backs, which results in a happier end user.
  • For the end user, utilizing smoke detectors listed to the 7th Edition of UL 268 gives peace of mind knowing that less disturbance to building occupants and business operation, and quicker detector response in the event of a fire, are on the horizon.

In conclusion, although manufacturers are not yet required to adopt the 7th Edition of UL 268, there are early adopters whose current system smoke detectors meet the new testing criteria and are readily available for use. These state-of-the-art devices offer advantages to all parties involved in a fire alarm system related project: the design engineers, specifiers, distributors and installing contractors, and end users who will see the system through to the end of its life cycle. Having knowledge of the UL 268 changes which are forthcoming in the 7th Edition of the standard and its implications on the fire protection industry is important and should be understood and adopted by those in the industry.

Erik Jackvony, EITJackvony, EIT, is an associate engineer with Jensen Hughes, a fire protection engineering and code-consulting firm. He is located at the firm’s Warwick, RI Office. Jackvony’s responsibilities and skills include developing and reviewing fire alarm system, fire sprinkler system and life safety system design drawings and layouts, performing on-site field surveys to ensure system compliance and verify design layouts. He also performs fire protection system acceptance testing and commissioning as part of his responsibilities. Jackvony also performs life safety code evaluations, performing third part firestopping inspections, ADA compliance evaluations and miscellaneous code consulting including, but not limited to, experience using several NFPA, ICC and ASME codes.

Wayne D. Moore, P.E.Moore, P.E., CFPS, SET, FSFPE, F.NSPE, is a licensed professional fire protection engineer, as well as vice president with Jensen Hughes, and he is located in the firm’s Warwick, RI office. He currently serves as a Principal member and former Chairman of the NFPA 72-2016 Emergency Communications Systems (ECS) Technical Committee and is a Principal member of the NFPA 72 Correlating Committee. Moore is the Editor/Co-Editor of five editions of the National Fire Alarm Code Handbook®. In 2012, NFPA published his book, “Designing Mass Notification Systems – A Pathway to Effective Communications”. He is the 2009 recipient of the NFPA Standards Medal and the 2012 Recipient of the AFAA Lifetime Achievement Award.


Reducing Nuisance Alarms

Contributed by Edwards

A New Jersey university housing complex comprised of over 100 apartments was plagued by more than 60 nuisance alarms—mostly from cooking, and all logged during the 2018-2019 school year. Nuisance fire alarms were a weekly, if not daily, occurrence within this complex. Whenever an alarm sounded, the entire student housing unit had to be evacuated until the local fire department arrived, investigated, and restored the system. These nuisance alarms disrupted the occupants, and disciplinary actions were taken if an occupant did not evacuate from an adjoining unit during an alarm. An accident or injury during a false alarm evacuation could have presented a liability issue.

Solution: In an effort to reduce the rate, frequency and number of nuisance or false alarms, the university contracted with Franklin Alarm Co. of Franklinville, NJ, and they identified a solution—to install more than 100 newly UL-listed Edwards Signature SIGA-OSD Optica smoke detectors in the housing complex.

According to Joe Petsch, president of Franklin Alarm Co., the two-day installation on the first floor of the complex was not disruptive to the building occupants, and no system hardware or programming changes were required to replace the old units with new ones.

Results: Following installation in the housing units of 100 Edwards Signature Optica smoke detectors in April 2019, false alarms went down to zero on the first floor and have remained at zero into the first few months of the 2019-2020 school year. The one nuisance cooking alarm reported post-installation was from an older detector on the second floor.

Stored data analysis by Edwards of five Optica units revealed ongoing nuisance events from that time period that could have triggered nuisance alarms. However, because the newly-listed detectors could differentiate between the smoke signatures of nuisances and events that actually presented a threat, the detectors did not sound. This was further validated when those units were reinstalled and subsequently alarmed when subjected to a UL-listed aerosol smoke test.

In September 2018, Edwards became the first multi-criteria smoke detector manufacturer to receive certification to UL 268 Standard for Safety, Smoke Detectors for Fire Alarm Systems, 7th edition. Its Signature Optica smoke detectors are able to distinguish between different types of fires, enhancing the protection of people and property.

Read the December 2019 update from UL on smoke detectors at this link. Learn more about Edwards at www.EdwardsFireSafety.com.


Do you have a comment? Share your thoughts in the Comments section below or send an e-mail to the Editor at acosgrove@groupc.com.

Want to read more about facility management and safety?

Check out all the latest facility management news related to fire and life safety.

Facilities Management, FacilityBlog, Featured, FM Issue, In-Depth Articles, Magazine, Security & Safety

Certification, Edwards, FE-April-2020, fire alarm systems, fire alarms, fire detection, Fire Safety, Jensen Hughes, National Fire Protection Association (NFPA), nuisance alarms, smoke detection, Smoke Detectors

Sponsored Content
Featured Video

Webinars, Podcasts & Videos

crime scene

Listen Now: What To Do When Your Facility Becomes A Crime Scene

A business continuity analyst discusses steps FM teams need to consider after a crime has been committed in their buildings.

Facilities Teams, ARC Facilities Webinar

Did You Miss Our “Solving The Hidden Assets Challenge” Webinar?

Hidden assets can be a challenge for facilities teams. View this free video webinar on demand and learn how your team can retain knowledge and streamline operations.

Job Order Contracting: Accelerating the Projects that Matter

This proven single-solicitation process accelerates project delivery while satisfying local bidding requirements. Learn all about Gordian’s JOC solutions .

Receive the latest articles in your inbox

Share to...